Bund Water Control Unit and Oil Skimmer
For a significant reduction in waste disposal costs select our bund dewatering and oil skimming pump. Automatically removes rainwater from the bund sump. When oil is detected a secondary pump transfers the oil to a separate holding tank.
Product Details
Product Information
For a significant reduction in waste disposal costs select our bund dewatering and oil skimming pump. Ideal for both manned and unmanned sites, the bund dewatering and oil skimming pump system continuously monitor the condition of the bund, displaying the current status on the control panel. The unit operates in two ways:
When rainwater fills the sump to a pre-determined level the pump automatically operates to remove non-contaminated water (rainwater containing less than 1ppm of oil per litre) out of the bund into the surface water drainage system.
If floating oil is present this is automatically pumped from the sump to a separate holding tank within the bund. Once the recovery tank is full an alarm will sound notifying that the tank requires emptying. The pump will still automatically remove rainwater.
Specification
- 1no 230V Mains Powered Bund Water Control Unit Panel
- Pump assembly stand
- 1no Junction Box
- Anti-siphon device
- 1no Water Pump and Probe set (c/w 5m Flyleads)
- 1no 230v Oil only Pump
- 1no Lifting Rope
Benefits
- Safe, dry working environment
- Maintains bund capacity
- Use in hazardous and non-hazardous zones
- Reduce maintenance and management time
- No civil works required
- Alarm situation relayed from remote locations
- Low maintenance
- Standard and ATEX-approved versions
- 24/7 automated monitoring and dewatering
- Claxon, beacon and GSM alarm notification
Installation, Commission and Service
Within the contracted service visit, we will be undertaking the following:
Bund Water Control Unit
- Take note of the display and record.
- Disconnect from mains supply.
- Check PCB for any signs of damage
- Check links on the Bund Water Control Unit PCB are in the correct position for standard operation ie. Pump inhibit on Deadstop, Pump enable on Float Switch
- Check all cables are still connected and are wired correctly
- Clean probes and ensure that the conductivity area is free from debris, oils and grease
- Clean and maintain filter and pump area
- Check sump area is free from debris
- Check “High Water” alarm o/p.
- Check “High Oil” alarm o/p.
- Check “High Level” alarm o/p.
- Check “Pump Failure” alarm o/p
- Extend the service warranty for a further 12 months from the visit date.
All the above steps are vital for any company to meet the Environmental Agencies Guidelines (PPG2) and the Oil Storage Regulations 2001 for efficient pollution prevention control and to enable your equipment to function correctly.
Product Downloads
Compare Models
Models |
Bund Water Control UnitView Product |
BWCU SkimmerView Product |
BWCU Semi ATEXView Product |
BWCU ATEXView Product |
---|---|---|---|---|
Doc 3 Pump 165 Litres a Minute | Pump up to 7 metres in height | 7 metres Head | 7 metres Head | 7 metres head |
Doc 7 Pump 230 Litres a Minute | Pump up to 12 metres in height | 11 metres Head | 11 metres Head | 11 metres head |
1 Pump | ||||
2 Pump (Duty Assist) | ||||
ATEX Pump | ||||
GSM Capability | ||||
Beacon | ||||
BMS Connection | ||||
Max Cable Length | 200 metres | 200 metres | 200 metres | 200 metres |
Installation & Commission | ||||
Service Package | ||||
Bund Water Separator |
Enquire Now
If you’re interested in discovering how we can help protect your business with our range of products and services, fill in the form and a member of our team will get in contact with you to discuss further.